Sign In | Join Free | My gimpguru.org |
|
Brand Name : Fenigal/OEM
Model Number : DCG
Certification : CCC, CE etc.
Place of Origin : China
MOQ : 12pcs / 1doz.
Price : Negotiate
Payment Terms : T/T, Western Union
Supply Ability : 200,000 pcs/month
Delivery Time : 2~15days
Packaging Details : standard in carton box
Model : DCG
Pole(s) : 2,4
Volt : 220~240VAC, 380~400VAC
Hz : 50~60Hz
Phase : 1/3
Standard : EN/IEC61008
Rated conditinal short circuit capacity : 6000A
Earth leakage current : 30mA, 100mA, 300mA
Case material : Nylon 66 recylable
Wiring : terminal block, busbar duct etc. IP20B
Electric shock protection : Class II
Mechanical life : 10,000
Electrical life : 4,000
DCG series Residual current circuit breaker(without over-current protection) is suitable for the line of A and S 50/60Hz, voltage 240V(2pole)/415V(4pole), rated current up to 63A.When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will cut off the power rapidly to protect human safety and prevent the accident due to the current leakage.It can be used as infrequent changeover of the line in normal situation.It is applicable to industrial site, commercial site, tall building and civil house.
It complies with standard of IEC/EN61008.1 and GB16916.1.Each phase of conductor at the circuit breaker passes through the zero-sequence current transformer, and the secondary side of coil connects with the electromagnetic tripper.Under normal condition, the vector sum of each phase of current passing through zerosequence current transformer is zero.The flux of the zero-sequence current transformer is zero.And the secondary output voltage is zero and the circuit breaker doesn't zero, and the zero-sequence current transformer would produce the magnetic flux, and the secondary side of coil would output the voltage.Once the leak current increases to drive the output voltage at the secondary side to grow to certain level, the electromagnetic release would activate to drive the operation mechanism to act to break the contact that connects the power, finally to realize the leak protection.
Newest type GE DCG RCCB
Application:
1. For protection against risk of fire due to live to earth fault where fault current is insufficient to cause over-current protection device to operate
2. For protection against risk of shock from indirect contact with equipment suffering a live to earth fault.
3. For protection against shock in potentially hazardous environment
4. As supplementary protection against shock from directly touching live parts
Note: An RCCB must not be used as the sole means of protection against touching live parts
Specification:
Rated working voltage: 240/415V
Rated frequency: 50/60Hz
Rated working current: 16, 20, 25, 32, 40, 50, 63, 80, 100A
Rated residual operating current: 0.03, 0.1, 0.03A
Sensibility: AC Type
Model NO. CGE RCCB Breaking Capacity Low Voltage Circuit Breakers Operation Electric Type Speed Normal Type Circuit Breaker Arc-extinguishing Medium Air Installation Fixed Structure Conventional Circuit Breaker Certification CE Body Material PA66 The Inside Parts IEC Standard Accessaries Type Circuit Breaker Function Overcurrent Protection Trademark Fenigal/OEM Specification IEC1008, GB16916, BS EN61008 Origin China Wenzhou |
![]() |
DCG RCCB 63A 30mA 2P 4P Industrial Circuit Breaker Images |